  1. Pubblicazioni

Performance assessment of seawater cooled chillers to mitigate urban heat island

Articolo
Data di Pubblicazione:
2020
Abstract:
Urban heat island (UHI) phenomenon, nowadays accentuated by global warming, is growing its negative influence
on urban resilience, building energy budget and human comfort during summer. To reduce UHI effect,
mitigation strategies are normally focused on actions related to urban design like the use of high reflectivity
surfaces and increase of vegetation. But, as concerns building anthropogenic heat, the benefits of a possible
reduction of the heat released by air conditioning systems to neighborhoods are often underestimate. An effective
solution consists in transporting the heat emitted by chiller condensers elsewhere by using water as heat
transfer fluid. The systematic use of seawater to cool chillers in an urban area of a coastal city was investigated.
The modification of the UHI phenomenon was studied as well as the consequences on building cooling demands
and chiller performances assessed in dynamic conditions. Urban weather files in presence of different types of
chillers were elaborated by Urban Weather Generator model. Building cooling demands in the area were
evaluated by using archetype modeling approach and EnergyPlus model. The algorithm adopted to assess chiller
performances takes into account also the effect of part load working condition. The comparison of seawater
cooled chillers technology versus the more diffuse use of air cooled chillers highlights a significant UHI effect
reduction which reaches 57% during the night. As regards cooling demand increment caused by UHI, with
seawater cooled chillers it is reduced of 58%. In the end, thanks to lower demand and higher chiller efficiency,
seawater cooling chillers achieve an energy saving of 23.5%. Therefore this solution can foster the urban resilience
and sustainability with an increasing contribution in front of the future climate scenario. Therefore, the
introduction of a district cooling network is an important iUHI mitigation strategy and its feasibility would have
to be always verified between the possible actions.
Tipologia CRIS:
1.1 Articolo su Rivista
Keywords:
Urban heat island Seawater cooled chillers Resilient city Urban weather model Anthropogenic heat District cooling network
Elenco autori:
Schibuola, Luigi; Tambani, Chiara
Autori di Ateneo:
EnerCity | Energia e Città
SCHIBUOLA LUIGI
TAMBANI CHIARA
Link alla scheda completa:
https://air.iuav.it/handle/11578/295640
Link al Full Text:
https://air.iuav.it//retrieve/handle/11578/295640/114707/pub%20234%20ATE%202020%20Performance%20assessment%20of%20seawater%20cooled.pdf
Pubblicato in:
APPLIED THERMAL ENGINEERING